Coaxial protection device for N connection up to 6 GHz: Male/female

Item no. 5093998 | EAN 4012196463831

  • 5-year warranty
  • Transition from LPZ 0 to LPZ 2
  • TV applications
  • SAT-TV applications
  • Installation electrotechnical expertise

Coaxial data cable protection devices for transmission and reception technology
• With N-Connector, male/female
• High impulse current load capacity: 2.5 kA (10/350)
• Simple mounting (adapter), m = connector, w = socket
• Low protection level at high current loads
• Optimum transmission behaviour:
- Low reflection behaviour
- Bandwidth-optimised for secure transmission up to 6 GHz
• Available in 50 Ω technology

Application: For example: SAT-TV C band, WiMAX, WLAN applications, DVB-T2

All types

All types

Types Highest
continuous
voltage
AC
Maximum
continuous
voltage
DC
Number
of poles
Connec-
tion
system
Item no. Quantity SSU
DS-N-6 M/W 50 V 70 V 1 N 5093998
1 piece
Coaxial protection device for N connection up to 6 GHz: Male/female
Coaxial protection device for N connection up to 6 GHz: Male/female

Coaxial protection device for N connection up to 6 GHz: Male/female

Item no. 5093998

Data sheet, 0.19MB, pdf
Download

Technical data

Arrestor monitoring no
Category Type 1+2 / D1+C2
SPD to IEC 61643-21 Class I+II / D1+C2
Number of poles 1
Insertion loss ≤0,1 dB
Explosion-tested version no
Telecommunications contact no
Total discharge current (8/20) 10 kA
Total discharge current (10/350) 5 kA
Frequency range 0 - 6 GHz
Frequency range 0 - 6000 MHz
Cut-off frequency 6000 MHz
Maximum continuous voltage AC 50 V
Maximum continuous voltage DC 70 V
Insulation resistance >1 GΩ
Impulse discharge current (10/350) 2.5 kA
Capacity (wire-wire) <10 pF
Capacity (wire-earth) <20 pF
Lightning protection zone LPZ 0→2
Rated current 10 A
Nominal load current AC 7 A
Nominal load current DC 10 A
Installation type Connector/cable adapter
Testing standard IEC 61643-21
Transmission power 80 W
Return loss ≥22 dB
Shielding connection available Yes
Shield connection Direct
Protection rating IP65/67
Protection level <750 V
Protection level wire-wire <750 V
Protection level wire-earth <750 V
Signalling on device None
Connection system N
Impulse durability wire-wire C2: 10 kV / 5 kA (8/20µs)
Impulse durability wire-earth C2: 10 kV / 5 kA (8/20µs)
Temperature range -40 - +80 °C
Wave resistance 50 Ω

Dimensions

Length 49 mm
Width 22.8 mm
Height 22.8 mm
Invitation to tender text

Invitation to tender text